Siemens SINAMICS S120 Installation And Start-Up Manual page 155

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Terminals for "Safe standstill"
The "Safe standstill" function is selected/deselected separately for each drive via
the terminals on the Control Unit and Motor Module.
S Control Unit
The required input terminal for "Safe standstill (SH)" is selected via the BICO
interconnection (BI: p9620).
Digital input DI 0 ... DI 7 on the Control Unit can be used as a signal source.
S Motor Module
The input terminal for "Safe standstill (SH)" is terminal "EP" ("Enable pulses").
Both terminals must be activated simultaneously, otherwise a fault is output.
X122.x
X132.x
DI x
r0722.x
M
Monitoring channel
Control Unit
Monitoring channel
Motor Module
safety_sh.vsd
Fig. 5-1
Terminals for "Safe standstill"
Grouping drives
To ensure that the function can be triggered simultaneously for more than one
drive, the terminals for the corresponding drives must be grouped together as fol-
lows:
S Control Unit
By connecting the binector input to the joint input terminal on the drives in one
group.
S Motor Module
By wiring the "EP" terminal on the individual Motor Modules in the group.
E Siemens AG, 2004. All rights reserved
SINAMICS S120 Installation and Start-Up Manual, 12/04 Edition
Control Unit
DRIVE–CLiQ
BI:
p9620
X21/X22
1
2
3
4
SINAMICS Safety Integrated (Booksize)
Motor Module
DRIVE–CLiQ
DRIVE–CLiQ
U2
V2
Temp +
W2
Temp –
EP +24 V
BR+
BR–
EP M
Safe standstill (SH)
G
M
~
3
5-155