750-636 [DC Drive Controller]
Configuration of the I/O Module via the Parameter Channel
2.1.1.10.6.1.3

Factory Default (3)

The parameter data set Factory Default (3) offers users the possibility to load a
parameter set that allows for a well-defined operating state of the module, if
necessary.
2.1.1.10.6.2

Password Protection

In order to save the parameter data set User Settings (2), enter password
0x1235 into register 31.
NOTICE:
The module does not automatically reset passwords. Without another write
command to register 31, they will remain valid until the power down.
The parameter data set Factory Default (3) may be only modified
(written/changed) by WAGO Kontakttechnik GmbH & Co. KG.
2.1.1.10.6.3

Changing the Parameter Data Sets

Fig. 2.1.1-31: Accessing the parameter data sets
2.1.1.10.6.3.1

Actual (1)

The parameter data set Actual (1) is changed by a write access via module
parameter channel (registers 56 and 57).
Read Access via
Parameter Channel
Write Access via
Parameter Channel
Actual
(1)
User Settings
(2)
Factory Default
(3)
g063605e
WAGO-I/O-SYSTEM 750