Process Image
4.3.1.2
Signal Types "±10 V", "±200 mV" "±20 mA", Two's complement

(Default)

Only one signal type per channel can be set as operating mode via the
commissioning tool.
Table 30: Signal Types "±10 V", "±200 mV", "±20 mA", Two's Complement
Measuring range
±10 V
n.a.
Neg. sensor overload
< −10.4
Underrange
−10.0
−6.0
−2.0
0.0
2.0
6.0
10.0
Exceeding
> 10.4
Sensor overload
n.a.
1)
When underrange / overrange limit is ON
2)
When wire break / overload diagnostics is ON
Manual
Version 1.0.2
±200 mV
±20 mA
n.a.
< −22.0
1000.0000.0000.0000
2)
< −210.0
< −21.0
1000.0000.0000.0000
1)
−200.0
−20.0
1000.0000.0000.0000
−120.0
−12.0
1011.0011.0011.0011
−40.0
−4.0
1110.0110.0110.0110
0.0
0.0
0000.0000.0000.0000
40.0
4.0
0001.1001.1001.1001
120.0
12.0
0100.1100.1100.1100 0x4CCC
200.0
20.0
0111.1111.1111.1111
1)
0111.1111.1111.1111
> 210.0
> 21.0
2)
0111.1111.1111.1111
n.a.
> 22.0
WAGO I/O System 750 XTR
750-471/040-000 4AI U/I Diff Galv XTR
Process value
Binary
Hex.
0x8000
0x8000
0x8000
0xB333
0xE666
0x0000
0x1999
0x7FFF
0x7FFF
0x7FFF
Status
Error
byte hex.
LED
Dec.
−32768
0x50
on
−32768
0x41
on
−32768
0x00
off
−19661
0x00
off
−6554
0x00
off
0
0x00
off
6553
0x00
off
19660
0x00
off
32767
0x00
off
32767
0x42
on
32767
0x50
on