2.1.1.10.2.3
Prestop_Neg
Parameter
address
Prestop value negative direction [0 ... 65535]
The configured value determines the prestop value to be used for optimization during a
positioning operation in negative direction if the option is enabled in the control byte of the
process image.
The format of the value is a 16-bit wide unsigned integer in the value range of 0 to 65535.
1 ... 65535:
100:*
* factory setting
2.1.1.10.2.4
Target_Window
Parameter
address
Tolerance range [0 ... 65535]
The configured value determines the size of the tolerance range during a positioning
operation. The range is defined with +/- around the setpoint position.
The format of the value is a 16-bit wide unsigned integer in the value range of 0 to 65535.
0:
1 ... 65535:
10:*
* factory setting
WAGO-I/O-SYSTEM 750
I/O-Modules
Configuration of the I/O Module via the Parameter Channel
Function
2
Prestop_Neg
Prestop value during positioning operations
Default prestop value negative direction
Function
3
Target_Window
Positioning must stop with setpoint position = actual position.
Positioning can stop within the tolerance range.
Default tolerance range
750-636 [DC Drive Controller]
Access
Factory setting
R/W
Access
Factory setting
R/W
• 45
0x0064
0x000A