2.1.1.10.3.2

Register Structure

2.1.1.10.3.2.1

Parameter data (register 56)

Register 56 contains the parameter data to be read or written. Depending on
the access type, either the I/O module (read parameters) or the fieldbus
coupler (write parameters) will write data to the register.
Bit
Parameter
Bit
Parameter PRM15 PRM14 PRM13 PRM12 PRM11 PRM10
PRM0 ... PRM15
2.1.1.10.3.2.2

Communication control (register 57)

Parameter channel control and diagnostics are done via register 57.
The following data is written by the application and read by the module:
Bit
Request
parameter
Bit
Request
parameter
A0 ... A7
TGL_MS
PRM_RW
MORE_PRM
RES
WAGO-I/O-SYSTEM 750
I/O-Modules
Configuration of the I/O Module via the Parameter Channel
Register 56, parameter channel register 0
7
6
5
PRM7
PRM6
PRM5
15
14
13
Parameter data bit 0 to bit 15
Register 57, parameter channel register 1
7
6
5
A7
A6
A5
15
14
13
TGL_
PRM_
MORE_
MS
RW
PRM
0 ... 255: Word address of the parameter to be read/written.
0/1:
Toggle bit to release new instructions from the application to the
module. If TGL_SM and TGL_MS have the same status, no new
instruction has been released yet. If the flags have different
statuses, a new instruction has been released and is currently
being processed.
0:
Parameter data of A7...A0 is read
1:
Parameter data is written to A7...A0
0:
End of parameter transmission
1:
More parameter data to follow
Reserved for expansions
750-636 [DC Drive Controller]
4
3
2
PRM4
PRM3
PRM2
12
11
10
4
3
2
A4
A3
A2
12
11
10
RES
RES
RES
• 53
1
0
PRM1
PRM0
9
8
PRM9
PRM8
1
0
A1
A0
9
8
RES
RES