Field and system levels are electrically isolated.
Individual I/O modules can be arranged in any combination when configuring
the fieldbus node. An arrangement in groups is not necessary.
The DC Drive Controller receives the 24 V DC supply voltage for the field
level via an upstream I/O module or a supply module. Power connections are
made automatically from module to module via internal power jumper
contacts when snapped onto the DIN rail.
CAUTION:
The maximum current that is permitted to flow through the power jumper
contacts is 10 A. When configuring the system, the total current should not
be exceeded. If this occurs, an additional supply module must be used.
The DC Drive Controller can be operated with all of the couplers and
controllers in the WAGO-I/O-SYSTEM 750 Series.
2.1.1.3

Connectors

Fig. 2.1.1-2: Connecting
elements
WAGO-I/O-SYSTEM 750
I/O-Modules
E+ E-
E-
E+
A
B
B
A
P
P
A+ A-
A+
A-
750-636
g063603x
750-636 [DC Drive Controller]
Connector
Function
Input for positive limit switch
E+
(break/make contact configurable)
Input for negative limit switch
E-
(break/make contact configurable)
Input for the A signal from the magnetic
A
transmitter (negative switching)
Input for the B signal from the magnetic
B
transmitter (negative switching)
Input for the preset switch
P
(break/make contact configurable)
A+
Motor connection +
A-
Motor connection -