String "MO<p1><p2><p3><p4><p5><p6>" (Machine command set digital out)
Parameter
p1
p2
p3
p4
p5 and p6
SIMATIC MV420 / SIMATIC MV440
Operating Instructions, 04/2013, A5E02371045-06
Process interfacing via an automation system (PLC, PC)
Meaning
Number of the logical external signal.
Two displayable ASCII characters with value "1" to "4"
•
–
Corresponds to "EXT_1", "EXT_2", "EXT_3" and "EXT_4"
Level of the signal
ASCII characters with the value "0" to "2".
•
–
0: Set level statically to "low".
–
1: Set level statically to "high".
–
2: Set level for configured pulse time to "high".
Link type
ASCII characters with the value "1" to "7"
•
–
1: Logical "OR"
–
2: Logical "AND"
–
3: Logical "Exclusive OR"
–
4: no link
–
5: Logical "OR not"
–
6: Logical "AND not"
–
7: Logical "Exclusive OR not"
Logical signal linked to.
If p3 = "4", the parameter has no significance.
ASCII characters with the value "0" to "5"
•
–
0: Logical signal "IN_OP"
–
1: Logical signal "TRD"
–
2: Logical signal "RDY"
–
3: Logical signal "READ"
–
4: Logical signal "MATCH"
–
5: Logical signal "NOK"
Reserved, must be "0" to retain upwards compatibility.
10.6 Control via TCP/IP and RS-232