AR6181-MX AR6182-MX Card reader AR6181-MX, AR6182-MX Installation and Configuration 6FL7170-8BK 6FL7170-8BL RS485: CerPass- and UCI-Protocol Clock/Data Interface: Omron and Wiegand Fire & Security Products Siemens Building Technologies...
Page 2
Thank you for deciding to purchase the AR618x-MX. We hope you are completely satisfied with this product. If you have any questions or comments please feel free to contact your local SIEMENS branch, who will be happy to help. The ID card readers AR6181-MX and AR6182-MX (with keypad) are new proximity ID card readers in a Square housing, part of the new Access reader range.
ID number – ASCII format RS485 – CerPass reader protocol ....38 10.2.6 ID number – ASCII format RS485 – UCI reader protocol ......38 10.2.7 ID number – BCD format RS485 – CerPass reader protocol ....39 Siemens Building Technologies Fire & Security Products 12.2004...
Page 4
11.1.2 Wiegand ....................45 11.2 Dimensions for flush mounting..............46 11.3 Dimensions for surface mounting with distance frame ......47 11.4 Addressing / Address setting: Mifare 1k ..........48 11.5 EC Declaration of Conformity..............49 Keyword index..................50 Siemens Building Technologies Fire & Security Products 12.2004...
If an operating display goes out, this does not necessarily mean that the unit is disconnected from the mains and has no power. If you are working on an open device, remember that live components may be exposed. Siemens Building Technologies Fire & Security Products 12.2004...
1 x housing; upper part with reader electronic and front foil 1 x housing; lower part with connection board 1 x distance frame 1 x accessory bag 1 x installation instructions 1 x repair form 3 x gasket Siemens Building Technologies Fire & Security Products 12.2004...
(number 0-9, C and E) Legend: UID – Unique card number, S/B – data out of a sector/block, B – data out of a block, MAD – Mifare Application Directory Siemens Building Technologies Fire & Security Products 12.2004...
Insert a screwdriver into the two points on the side of the reader housing between the top and bottom sections of the housing (2). Remove the top section of the housing from the bottom section. Fig. 2 Opening the housing Siemens Building Technologies Fire & Security Products 12.2004...
Note: The maximum torque of the safety screw is 1.5 Nm. Socket connector X3 Fig. 3 Back view of the bottom section of the housing with the terminal board snapped in Siemens Building Technologies Fire & Security Products 12.2004...
Three gaskets in the reader package Usage Gasket 1: Between reader and mounting surface, with or without distance frame Gasket 2: Between housing base and distance frame Gasket 3: Gasket for safety screw Siemens Building Technologies Fire & Security Products 12.2004...
Page 11
Whether the reader will be mounted with or without distance frame, the gasket 3 has to be used in both cases. The accessory pack includes one gasket 3 as a reserve. Fig. 7 Use of gasket 3 Siemens Building Technologies Fire & Security Products 12.2004...
The reader is connected using the terminal board at the bottom section of the housing. Fig. 8 Terminal board Terminal Function Strip Description AR6181-MX/AR6182-MX card reader RS485 Bus Clock/Data interface Omron Wiegand + / ~ Power supply - / ~...
The cable length is limited to a maximum of 100 cm. CLK / D0 CLOCK UCI-Box DAT / D1 AR6181-MX DCU-3 GND / +V GND / +V IN1 / IN2 IN1 / IN2 Fig. 10 Connection using Clock/Data interface Siemens Building Technologies Fire & Security Products 12.2004...
The address option of the reader interface and door controller must be considered. DIP 1 DIP 2 DIP 3 DIP 4 Bus address 0-15 1-16 Tab. 2 Bus address: addressing taking into account the interface Siemens Building Technologies Fire & Security Products 12.2004...
Omron (Magstripe Track II) RS485 point-to-point Configuration mode x – don’t care, see tab. 2 Selection of communication interface Tab. 3 Note: In RS485 bus operation, DIP 4 is LSB of the reader's bus address. Siemens Building Technologies Fire & Security Products 12.2004...
In this case, the ID number is written according to the Wiegand format rules (26 or 37 bit Wiegand format, others may be possible). No reaction or malfunction will be at the reader AR6181-MX if other coded cards are presented.
Page 17
The ID number is an information written by the user into the read/write area of the qualified transponders / cards (Write areas sector/block or block within qualified transponders / cards). No reaction or malfunction will be at the reader AR6181-MX if other coded cards are presented. DIP 7...
7-bit ASCII Wiegand Without / with PIN Detailed knowledge about the content to be read and the format, as well as a possibly existing access protection, on the ID card is required. Siemens Building Technologies Fire & Security Products 12.2004...
If UID is greater than 40 bits (5 bytes), the part to be analyzed has to be selected accordingly; see configuration parameters C05, C06 in chapter 10.1 Config or ConfigCard parameters. 8.1.2 ISO14443A+B Proximity read range Type Manu- Block Access block facturer length (byte) my-C Infineon ● (SLE66CL160S) Siemens Building Technologies Fire & Security Products 12.2004...
Data from sector/block (direct), e.g. ID number (for more information please refer to chapter 8.2.2). Data from sector via MAD (indirect), e.g. ID number (for more information please refer to chapter 8.2.2). Siemens Building Technologies Fire & Security Products 12.2004...
Depending on the transponder type used, access to the data is via "public mode" (direct addressing of memory block without access protection) or "safe mode" (direct addressing of memory block with access protection authentication). Siemens Building Technologies Fire & Security Products 12.2004...
(e.g. in case of Mifare MifareApplicationDirectory). Access to a block with written data is to be set with the different configuration parameters of the card reader AR6181-MX. Parameters to access a personalized block: Block address (for more information please refer to chapter 10 under SL_BLOCK).
(e.g. facility code, ID number). The content of a block consists of binary values with defined bit length. For output, the Wiegand format is transferred 1:1 (Wiegand interface) or is interpretatively prepared and the binary values/contents are transferred as decimal equivalents. Siemens Building Technologies Fire & Security Products 12.2004...
Within configuration mode you may check or change some additional settings or get information out of the reader with a terminal program, e.g. HyperTerminal. For more information please refer to chapters 9.2 and 9.3. Siemens Building Technologies Fire & Security Products 12.2004...
Launch the terminal program via the Windows Start menu and then select Programs-> Accessories-> Communication ->HyperTerminal. When started successfully this dialog box opens: Enter a name such as Config_AR618x-MX into the name field. Siemens Building Technologies Fire & Security Products 12.2004...
Page 26
Confirm by clicking on OK. Now select the following parameters: Bits per second 9600 Data bits Parity None Stop bits Flow control None Confirm by clicking on OK. "HyperTerminal" has been started successfully. Siemens Building Technologies Fire & Security Products 12.2004...
Select "Properties" from the "File" menu. The following dialog box opens: Select the following parameters on the "Settings" tab: Click on The following dialog box opens: Specify the following parameters in the dialog box: Siemens Building Technologies Fire & Security Products 12.2004...
Page 28
The following dialog box opens: Select the desired file, which you have edited. (Please see chapter 9.1 Defining parameters). Click on the Open button. The following dialog box opens: The data were then successfully loaded. Siemens Building Technologies Fire & Security Products 12.2004...
Start the program “HyperTerminal”. See also chapter 9.2 Launching the terminal program Enter the command „FIRMWARE“. The message START BOOTLOADER is displayed (see figure) Select „New Connection“ from the „File“ menu. The following dialog box opens: Siemens Building Technologies Fire & Security Products 12.2004...
Page 30
Bits per second 38400 Data bits Parity None Stop bits Flow control None Confirm by clicking on OK. After pressing the Return key the following message is displayed: Enter the command „FLASHALL“. Siemens Building Technologies Fire & Security Products 12.2004...
Page 31
Select „Send File“ from the „Transfer“ menu. The following dialog box opens: Enter the desired file into the filename field and Xmodem into the Protocol field. Click on „Send“ to send the file. Siemens Building Technologies Fire & Security Products 12.2004...
Card reader configuration Reader interface The card readers AR6181-MX and AR6182-MX have to be connected via a RS485 bus interface, 2-wire, to the reader interface of the interface unit (e.g. DRI) or a door controller. For that a 4-wire, twisted pair, shielded cable is required. One pair is for the 2-wire RS485 party line and the other pair for power supply of the reader.
ISO14443-A+B + 15693 transponder CONFIG_CARD 0x00 After a power on reset, the configuration mode is active for 5 seconds. 0x01 The configuration mode is active during normal operation if driver A has been activated. Siemens Building Technologies Fire & Security Products 12.2004...
Page 34
First data nibble to be transferred from the ID number (with ASCII data, the values have to be divisible by 2) ID_LEN 0x01 ... 0x20 Number of data nibbles to be transferred (with ASCII data, the values have to be divisible by 2) Siemens Building Technologies Fire & Security Products 12.2004...
Page 35
"nn" digits have been reached If the BCD value exceeds the value range defined by "nn" the higher-order digits are truncated Data are transferred in the following order: CompanyCode (CC), FacilityCode (FC), CardNumber (CN) Siemens Building Technologies Fire & Security Products 12.2004...
Page 36
UID_MASK Masking the bit digits of the UID to be checked (80-bit) UID_Pattern Test pattern for UID (matching of the masked UID parts) (80-bit) Siemens Building Technologies Fire & Security Products 12.2004...
CARD_TEC, TAG_BEEP, TAG_LED, CONFIG_CARD Transferred: ID card data: Card number in ABA format (5-bit), 13 digits, aligned right, filled with zeros PIN: see Setting PIN input Clock / Data - Omron Interface in chapter 10.3.3. Siemens Building Technologies Fire & Security Products 12.2004...
ID card data: 16 characters in ASCII format of which 13 are ID card number characters, aligned left, filled with zeros (0x30) PIN: see Setting PIN input UCI Reader Protocol in chapter 10.3.2. Siemens Building Technologies Fire & Security Products 12.2004...
16 characters in ASCII format of which 13 are ID card number characters, aligned left, filled with zeros (0x30) – (telegram identifier: Kg) PIN: see Setting PIN input Clock / Data - Omron Interface in chapter 10.3.3. Siemens Building Technologies Fire & Security Products 12.2004...
BCD or ASCII values; any possibly required leading zeros are to be considered during parameterization (WG_xx_nn parameter) PIN: see Setting PIN input UCI Reader Protocol in chapter 10.3.2. Siemens Building Technologies Fire & Security Products 12.2004...
BCD values in ABA format (5-bit); any possibly required leading zeros are to be considered during parameterization (WG_xx_nn parameter) PIN: see Setting PIN input Clock / Data - Omron Interface in chapter 10.3.3. Siemens Building Technologies Fire & Security Products 12.2004...
Use of default buffer length, depending on the interface. For more information please refer to PIN_BUF in chapter 8. 0x01 ... 0x06 Number of permissible PIN digits, autom. completion if number of digits reached; otherwise finish with E key! Siemens Building Technologies Fire & Security Products 12.2004...
PIN input with ID card number ID card number with PIN code, separator is D (0x0D), in BCD format A different way of handling the PIN input is listed with the individual settings. Siemens Building Technologies Fire & Security Products 12.2004...
If reading access keys for the sector (directly addressed access) or the reading access keys for the MAD sector and the data sector (indirect access via MAD) are not loaded into the card reader, the Mifare cards cannot be read by the card reader. Siemens Building Technologies Fire & Security Products 12.2004...
The characters/digits read out of cards (transponder) will be transmitted directly 1:1 (no change) without adding any information frames. If there is a special format required, the ID No. on the ID card can be adjusted. Siemens Building Technologies Fire & Security Products 12.2004...
Appendix 11.3 Dimensions for surface mounting with distance frame All dimensions in mm. Siemens Building Technologies Fire & Security Products 12.2004...
Technical specifications 7 Display elements 12 Terminal program 25, 29 Transponder 18 Data formats 22 Format Information 20 ASCII 23 Transponder types 16, 19, 21 BCD 22 Wiegand 23 Wiegand format 23 Siemens Building Technologies Fire & Security Products 12.2004...