Siemens SIMATIC MV440 Operating Instructions Manual page 261

Simatic ident code reader system
Hide thumbs Also See for SIMATIC MV440:
Table of Contents

Advertisement

Table 10- 30 Command data area (FB45: Data DB, RFID standard profile: TXBUF or RXBUF)
Address
0x0000
0x0001
0x0002
0x0003
0x0004
0x0005
0x0006
SIMATIC MV420 / SIMATIC MV440
Operating Instructions, 04/2013, A5E02371045-06
Process interfacing via an automation system (PLC, PC)
Value
0x08
0x1-0x4
0x0-0x2
0x1-0x7
0x0-0x5
0x0
0x0
10.3 Control with FB 45 and Ident profile
Meaning
Command identifier "Set digital out".
Number of the logical external signal.
Corresponds to "EXT_1", "EXT_2", "EXT_3" and
"EXT_4".
Level of the signal
0x0: Set level statically to "low".
0x1: Set level statically to "high".
0x2: Set level for configured pulse time to
"high".
Link type
0x1: Logical "OR"
0x2: Logical "AND"
0x3: Logical "Exclusive OR"
0x4: no link
0x5: Logical "OR not"
0x6: Logical "AND not"
0x7: Logical "Exclusive OR not"
Logical signal linked to.
If the link type is 0x4, the parameter has no
significance.
0x0: Logical signal "IN_OP"
0x1: Logical signal "TRD"
0x2: Logical signal "RDY"
0x3: Logical signal "READ"
0x4: Logical signal "MATCH"
0x5: Logical signal "NOK"
Reserved, must be 0x0 to retain upwards
compatibility.
Reserved, must be 0x0 to retain upwards
compatibility.
259