Diagnostics

7.10 LEDs on the Voltage Sensing Module (VSM) in the Active Interface Module

7.10
LEDs on the Voltage Sensing Module (VSM) in the Active Interface
Module
Table 7- 15
Meaning of the LEDs on the Voltage Sensing Module in the Active Interface Module
LED
Color
---
Green
Orange
Red
RDY
Green/
(READY)
red
Green/
orange
or
red/
orange
324
Status
Description
Off
The electronics power supply is missing or out of tolerance.
Steady light
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
Steady light
DRIVE-CLiQ communication is being established.
Steady light
At least one fault is present in this component.
Note:
LED is driven irrespective of the corresponding messages being
reconfigured.
Flashing light
Firmware is being downloaded.
0.5 Hz
Flashing light
Firmware download is being completed.
2 Hz
Waiting for POWER ON.
Flashing light
Component recognition via LED is activated (p0144).
2 Hz
Note:
Both possibilities depend on the LED status when activated via p0144 = 1.