Electrical installation
4.4 Connections
Auxiliary power module
Figure 4-4
Table 4- 3
X100, terminal block for tapping the auxiliary voltages
Terminal
1
2
3
4
5
6
The maximum load-carrying capacity of the auxiliary power supply system is 80 A according to IEC (or 80 A according to
UL).
Spring-loaded terminal, conductor cross section: single-wire and flexible cables 0.08 to 2.5 mm
Max. total current of all tapping terminals available
1)
At least two terminals are always available to the customer at terminal block -X100 for
tapping the auxiliary voltages.
70
Auxiliary power module with terminal blocks -X100, -X101 and 24 V DC fuse
Designation
Voltage tap
L1
Line voltage (for fan supply via transformer):
380 to 480 V 2 AC or
L2
500 to 690 V 2 AC (max. 759 V AC)
L1
230 V 1 AC (max. 265 V AC)
N
P24
24 V DC for the electronics power supply (max. 30
V DC)
M
Rated current
max. 16 A
max. 16 A
max. 10 A
2
Cabinet Modules
Manual, (GH5), 05/2010, A5E03263538A