Table 8- 13
Line supply voltage range
Table 8- 14
Line supply voltage range
NOTICE
If the terminals are not reconnected to the actual supply voltage, the internal power supply
will not be correct.
Cabinet Modules
Manual, (GH5), 05/2010, A5E03263538A
8.12 K76, auxiliary voltage generating unit in the Line Connection Module
Line voltage assignments for the internal power supply
(380 to 480 V 3 AC)
342 to 390 V
391 to 410 V
411 to 430 V
431 to 450 V
451 to 470 V
471 to 528 V
Line voltage assignments for the internal power supply
(500 to 690 V 3 AC)
450 to 515 V
516 to 540 V
541 to 560 V
561 to 590 V
591 to 630 V
631 to 680 V
681 to 759 V
Tap
Taps of the voltage matching transformer
380 V
400 V
415 V
440 V
460 V
480 V
Tap
Taps of the voltage matching transformer
500 V
525 V
550 V
575 V
600 V
660 V
1 to 14, terminals 12 and 13 are jumpered
690 V
1 to 15, terminals 12 and 13 are jumpered
(-T10) LH1 – LH2
1 - 2
1 – 3
1 – 4
1 – 5
1 – 6
1 – 7
(-T10) LH1 – LH2
1 - 8
1 – 9
1 – 10
1 – 11
1 – 12
Options
363