Siemens SINAMICS S120 Manual page 315

Modular motion control drive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

LED
Color
Red/
green
Orange
Green/
orange
or
red/
orange
DP
PROFIdrive
cyclic
operation
Green
Red
OPT
(OPTION)
Green
Red
RDY and
Red
DP
Cabinet Modules
Manual, (GH5), 05/2010, A5E03263538A
State
Flashing light
Control Unit is ready for operation.
0.5 Hz
However, there are no software licenses.
Flashing light
Updating the firmware of the DRIVE-CLiQ
0.5 Hz
components
Flashing light
DRIVE-CLiQ component firmware update
2 Hz
completed. Wait for POWER ON for the
components in question.
Flashing light
Component detection via LED is activated
1 Hz
(p0124[0]).
Note:
Both options depend on the LED status when
component detection is activated via
p0124[0] = 1.
Off
Cyclic communication has not (yet) taken place.
Note:
PROFIdrive is ready to communicate when the
Control Unit is ready to operate (see LED RDY).
Steady light
Cyclic communication is taking place.
Flashing light
Full cyclic communication is not yet taking place.
0.5 Hz
Possible causes:
The controller is not transferring any setpoints.
During isochronous operation, no global
control (GC) or a faulty global control (GC) is
transferred by the controller.
Flashing light
PROFIBUS master is sending incorrect
0.5 Hz
parameterization / configuration data
Flashing light
Cyclic bus communication has been interrupted or
2 Hz
could not be established
Off
The electronics power supply is missing or
outside the permissible tolerance range.
Component is not ready.
Option Board not installed or no associated drive
object has been created.
Steady light
Option Board is ready.
Flashing light
Depends on the Option Board used.
0.5 Hz
Steady light
At least one fault is present in this component.
Option board not ready (e.g. after switch on).
Flashing light
Bus error - communication has been interrupted
2 Hz
7.2 LEDs on the CU320-2 DP Control Unit
Description, cause
Diagnostics
Remedy
Obtain licenses
Carry-out POWER ON
for the components in
question
Adapt configuration
between master /
controller and CU
Remove fault
Check power supply
and/or component
Remove and
acknowledge fault
Remove fault
315

Hide quick links:

Advertisement

Table of Contents
loading