5.4 Active Line Modules

5.4
Active Line Modules
5.4.1

General information

Hazardous voltages are present in certain parts of this equipment during operation of the
cabinet unit.
Only qualified personnel may work on the cabinet.
Such personnel must be thoroughly familiar with all the warnings and maintenance
procedures for the cabinet described in the documentation provided.
The successful and safe operation of this cabinet is dependent on correct transport, proper
storage and installation, as well as careful operation and maintenance.
National safety regulations must be observed.
5.4.2

Description

Note
Refer to the layout diagrams (AO) and circuit diagrams (SP) provided on the customer DVD
supplied with the device for the arrangement of components and interfaces, and for wiring.
Active Line Modules can supply motoring energy and return regenerative energy to the
supply system.
Active Line Modules generate a regulated DC voltage that is kept consistent regardless of
fluctuations in the line voltage (the line voltage must range within the permissible tolerances).
In the factory setting, the DC voltage is controlled to 1.5 times the rms value of the rated line
voltage.
Active Line Modules draw a virtually sinusoidal current from the supply system and cause
virtually no line harmonic distortions.
Active Line Modules are suitable for connection to grounded (TN, TT) and non-grounded (IT)
supply systems. The following voltages and power ratings are available:
Line voltage
3 AC 380 ... 480 V
3 AC 500 ... 690 V
The power rating can be increased by connecting Active Line Modules in parallel.
158
DANGER
Rated power
132 ... 900 kW
560 ... 1400 kW
Manual, (GH5), 05/2010, A5E03263538A