Smart Line Modules
When the device is operated on an isolated line supply (IT line supply), the connection bar to
the interference suppression capacitor must be removed (e.g.: "1" in figure below).
With frame sizes HX and JX, you must remove the left-hand fan before removing the
connection bar (see chapter "Replacing components").
Figure 4-10
Removing the connection bar to the interference suppression capacitor in the Smart Line Module for frame
size JX
Cabinet Modules
Manual, (GH5), 05/2010, A5E03263538A
Verbindungsbügel zum Entstörkondensator
(hinter dem Lüfter)
Electrical installation
4.4 Connections