Siemens SINAMICS S120 Manual page 194

Modular motion control drive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Cabinet Modules
5.6 Chassis format Motor Modules
Minimum cable lengths for parallel connection and connection to a motor with a single-winding
system
NOTICE
The minimum cable lengths specified in the table below must be observed when two or
more Motor Modules are connected in parallel and there is a connection to a motor with a
single-winding system. If the cable length required cannot be achieved in the application,
provision must be made for a motor reactor (option L08).
Table 5- 31
Motor Modules, 510 ... 750 V DC
Order No.
6SL3720-1TE32-1AA3
6SL3720-1TE32-6AA3
6SL3720-1TE33-1AA3
6SL3720-1TE33-8AA3
6SL3720-1TE35-0AA3
6SL3720-1TE36-1AA3
6SL3720-1TE37-5AA3
6SL3720-1TE38-4AA3
6SL3720-1TE41-0AA3
6SL3720-1TE41-2AA3
6SL3720-1TE41-4AA3
Table 5- 32
Motor Modules, 675 ...1080 V DC
Order No.
6SL3720-1TG28-5AA3
6SL3720-1TG31-0AA3
6SL3720-1TG31-2AA3
6SL3720-1TG31-5AA3
6SL3720-1TG31-8AA3
6SL3720-1TG32-2AA3
6SL3720-1TG32-6AA3
6SL3720-1TG33-3AA3
6SL3720-1TG34-1AA3
6SL3720-1TG34-7AA3
6SL3720-1TG35-8AA3
6SL3720-1TG37-4AA3
6SL3720-1TG38-1AA3
6SL3720-1TG38-8AA3
6SL3720-1TG41-0AA3
6SL3720-1TG41-3AA3
194
Frame size
P
[kW]
rated
FX
110
FX
132
GX
160
GX
200
GX
250
HX
315
HX
400
HX
450
JX
560
JX
710
JX
800
Frame size
P
rated
FX
75
FX
90
FX
110
FX
132
GX
160
GX
200
GX
250
GX
315
HX
400
HX
450
HX
560
JX
710
JX
800
JX
900
JX
1000
JX
1200
I
[A]
rated rms
210
260
310
380
490
605
745
840
985
1260
1405
[kW]
I
[A]
rated rms
85
100
120
150
175
215
260
330
410
465
575
735
810
910
1025
1270
Manual, (GH5), 05/2010, A5E03263538A
Minimum length [m]
30
27
20
17
15
13
10
9
8
6
5
Minimum length [m]
100
90
80
70
60
50
40
30
25
25
20
18
15
12
10
8
Cabinet Modules

Hide quick links:

Advertisement

Table of Contents
loading