7.3 LEDs on the CBE20 Communication Board

7.3
LEDs on the CBE20 Communication Board
Table 7- 4
Meanings of the LEDs on the CBE20 Communication Board
LED
Color
Link port
-
Green
Activity port
-
Yellow
Fault
Red
Sync
Green
OPT on the
Control Unit
Green
Red
316
Status
Off
The electronics power supply is missing or outside the permissible
tolerance range.
Steady light
A different device is connected to port x and a physical connection exists.
Off
The electronics power supply is missing or outside the permissible
tolerance range.
Steady light
Data is being received or sent at port x.
Off
If the link port LED is green:
The CBE20 is operating normally, data is being exchanged with the
configured IO controller.
The response monitoring interval has elapsed.
Flashing
Communication is interrupted.
The IP address is incorrect.
Incorrect or no configuration
Incorrect parameter settings
Incorrect or missing device name
IO Controller not connected/switched off, although an Ethernet
connection has been established.
Other CBE20 errors
Steady light
CBE20 bus error
No physical connection to a subnet/switch.
Incorrect transmission rate
Full duplex transmission is not activated.
Off
If the link port LED is green:
Control Unit task system is not synchronized with the IRT clock. An
internal substitute clock is generated.
Flashing light
The Control Unit task system has synchronized with the IRT clock cycle
and data is being exchanged.
Steady light
Task system and MC-PLL synchronized with the IRT clock.
Off
The electronics power supply is missing or outside the permissible
tolerance range.
Communication Board either defective or not inserted.
Steady light
Communication Board is ready and cyclic communication is taking place.
Flashing light
The Communication Board is ready, but cyclic communication is not yet
0.5 Hz
taking place.
Possible causes:
At least one fault is present.
Communication is being established.
Steady light
Cyclic communication via PROFINET has not yet been established.
However, acyclic communication is possible. SINAMICS waits for a
parameterizing/configuration telegram