8.14.3.13

X535 digital outputs

Table 8- 26
Terminals X535
Terminal
1
2
3
An F-DO comprises two digital outputs and a digital input for the feedback signal
F-DO 3 = terminals 1, 2 and 3
Max. connectable cross-section: 1.5 mm²
Type: Screw terminal 1 (see Appendix A)
DI: Digital input; DO: Digital output
1)
Pure hardware delay
2)
Cabinet Modules
Manual, (GH5), 05/2010, A5E03263538A
Designation
Technical data
1)
DI 23
Voltage: - 3 V to +30 V
Typical current consumption: 3.2 mA at 24 V DC
Electrical isolation: Reference potential is terminal M1
The digital input is electrically isolated.
Input delay
- for "0" to "1": 30 μs (100 Hz)
- for "1" to "0": 60 μs (100 Hz)
Level (incl. ripple)
High level: 15 V to 30 V
Low level: -3 V to 5 V
DO 3+
0.5 A
Reference potential is terminal M1
DO 3-
0.5 A
Reference potential is terminal L1+, L2+ or L3+
Output delay
- for "0" to "1": 300 μs
- for "1" to "0": 350 µs
Total current consumption of all DOs: 2 A
Max. leakage current: < 0.5 mA
Switching frequency:
For resistive load: Max. 100 Hz
For inductive load: Max. 0.5 Hz
For lamp load: Max. 10 Hz
Maximum lamp load: 5 W
8.14 K87, Terminal Module TM54F
:
2)
:
2)
Options