Siemens SINAMICS S120 Manual page 348

Modular motion control drive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Options
8.9 K48, Sensor Module Cabinet-Mounted SMC20
X520 encoder interface
Table 8- 6
Encoder interface X520
Pin
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Connector type: 25-pin sub D connector (pin)
Risk of electric shock!
Only temperature sensors that meet the safety isolation specifications contained in
EN 61800-5-1 may be connected to terminals "+Temp" and "-Temp".
If these instructions are not complied with, there is a risk of electric shock!
348
Signal name
P encoder
M encoder
A
A*
Ground
B
B*
Ground
Reserved, do not use
Clock
Reserved, do not use
Clock*
+ Temp
P sense
Data
M sense
R
R*
C
C*
D
D*
Data*
Ground
- Temp
DANGER
Technical data
Encoder power supply
Ground for encoder power supply
Incremental signal A
Inverted incremental signal A
Ground (for internal shield)
Incremental signal B
Inverted incremental signal B
Ground (for internal shield)
Clock, EnDat interface, SSI clock
Inverted clock, EnDat interface,
inverted SSI clock
Motor temperature measurement KTY84-1C130
(KTY+)
Temperature sensor KTY84-1C130 / PTC
Sense input for encoder power supply
Data, EnDat interface,
SSI data
Ground for sense input for encoder power supply
Reference signal R
Inverted reference signal R
Absolute track signal C
Inverted absolute value signal C
Absolute track signal D
Inverted absolute track signal D
Inverted data, EnDat interface,
inverted SSI data
Ground (for internal shield)
Motor temperature measurement KTY84-1C130
(KTY-)
Temperature sensor KTY84-1C130 / PTC
Manual, (GH5), 05/2010, A5E03263538A