Mechanical installation
3.1 Important notes
Note
Notes regarding damage in transit:
• Carry out a thorough visual inspection of the SINAMICS S120 Cabinet Modules before
• Check that you have received all the items specified on the delivery note.
• Notify the shipping company immediately of any missing components or damage.
• If you identify any hidden defects or damage, contact the shipping company immediately
• If you fail to contact them immediately, you may lose your right to claim compensation for
• If necessary, you can request the support of your local Siemens office.
Damage in transit indicates that the cabinet was subject to unreasonable stress. The
electrical safety of the cabinet can no longer be ensured. It must not be connected until a
thorough high-voltage test has been carried out.
Death, serious injury, or substantial material damage can result if these factors are not
taken into account.
Inform Technical Support (hotline)
Commissioning must not be carried out, if an indicator has tripped. Please contact
Technical Support immediately.
If commissioning is carried out without prior inspection of the indicators, safe operation of
the converter cannot be guaranteed. This can result in death, serious personal injury or
material damage.
40
accepting the delivery from the shipping company. Pay special attention to transport
damage that is not readily apparent but indicated by the tilt and shock indicators.
and ask them to examine the cabinet.
the defects and damage.
WARNING
WARNING
Cabinet Modules