Siemens SINAMICS S120 Manual page 344

Modular motion control drive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Options
8.8 K46, Sensor Module Cabinet-Mounted SMC10
X520 encoder interface
Table 8- 5
Encoder interface X520
Pin
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Connector type: 25-pin sub D connector (pin)
Risk of electric shock!
Only temperature sensors that meet the safety isolation specifications contained in
EN 61800-5-1 may be connected to terminals "+Temp" and "-Temp".
If these instructions are not complied with, there is a risk of electric shock!
344
Signal name
Reserved, do not use
Reserved, do not use
S2
S4
Ground
S1
S3
Ground
R1
Reserved, do not use
R2
Reserved, do not use
+ Temp
Reserved, do not use
Reserved, do not use
Reserved, do not use
Reserved, do not use
Reserved, do not use
Reserved, do not use
Reserved, do not use
Reserved, do not use
Reserved, do not use
Reserved, do not use
Ground
- Temp
DANGER
Technical data
Resolver signal A (sin+)
Inverted resolver signal A (sin-)
Ground (for internal shield)
Resolver signal B (cos+)
Inverted resolver signal B (cos-)
Ground (for internal shield)
Resolver excitation positive
Resolver excitation negative
Motor temperature measurement KTY84-1C130 (KTY+)
Temperature sensor KTY84-1C130 / PTC
Ground (for internal shield)
Motor temperature measurement KTY84-1C130 (KTY-)
Temperature sensor KTY84-1C130 / PTC
Manual, (GH5), 05/2010, A5E03263538A