Siemens SINAMICS S120 Manual page 289

Modular motion control drive
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Description
The average service life of the device fans is approximately 50,000 hours. In practice,
however, the service life depends on other variables (e.g. ambient temperature, degree of
cabinet protection, etc.) and, therefore, may deviate from this value.
The fans must be replaced in good time to ensure the availability of the Cabinet Module.
Preparatory steps
● Observe the "five safety rules".
● Remove the protective cover.
● Allow unimpeded access.
Removal steps
The removal steps are numbered in accordance with the figure above.
1. Remove the busbars (12 screws).
2. Remove the retaining screws for the fan (3 screws).
3. Disconnect the supply cables (1 x "L", 1 x "N").
You can now carefully remove the fan.
CAUTION
When withdrawing it, ensure that you do not damage any signal cables.
NOTICE
Take care not to cut yourself on the sharp edges inside the cabinet.
Installation steps
Installing is the same as removing, however in the reverse order.
CAUTION
The tightening torques specified in the table "Tightening torques for connecting current-
conducting parts" must be observed.
The screw connections for the protective covers may only be tightened by hand.
Cabinet Modules
Manual, (GH5), 05/2010, A5E03263538A
Maintenance and servicing
6.4 Replacing components
289

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents