Send Data Word Allocation (3Rd Operand Of Pmcr(260)) - Omron CS1W-SCU21 Operation Manual

Hide thumbs Also See for CS1W-SCU21:
Table of Contents

Advertisement

K3T# Intelligent Signal Processor Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
The work allocation is similar to sequence No. 337 (Model Data Read (by Unit Number)).
General-purpose Command (Sequence No. 339 (Hex 0153))
Sends the specified data and writes the receive data to the receive data words. The characters such as "@",
FCS, terminators need not be set in the send and receive data words. These characters will be automatically
added for transmission and automatically removed before saving data.

Send Data Word Allocation (3rd Operand of PMCR(260))

First word of
send data
Receive Data Word Allocation (3rd Operand of PMCR(260))
Receive data
storage words
+0
Number of send data words
+1
Send data byte length
Send data
+2
+3
Send data
~
+249
Send data
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Send data byte length (4 digits BCD)
+2 to
Send data (ASCII)
+249
+0
Number of receive data words
+1
Receive data
+2
Receive data
+3
Receive data
~
Receive data
+249
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1 to
Receive data (ASCII)
+249
~
0003 to 00FA (3 to 250 decimal)
0001 to 01F0 (1 to 496 decimal)
Number of bytes of send data not including
@, the FCS, and the terminator.
ASCII code
Send data: 496 characters max.
~
0001 to 00FA (1 to 250 decimal)
ASCII code
Receive data: 498 characters max.
Appendix I
Data
Data
375

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-scu41