Omron CS1W-SCU21 Operation Manual page 348

Hide thumbs Also See for CS1W-SCU21:
Table of Contents

Advertisement

ES100# Digital Controller Protocol
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1 to 2
Fixed SP (8 digits BCD)
+3 to 4
Control output 1 pulse cycle
(8 digits BCD)
+5 to 6
Control output 2 pulse cycle
(8 digits BCD)
+7 to 8
Fuzzy strength (8 digits BCD)
+9 to 10
Cooling coefficient (8 digits BCD)
+11 to 12
Heater burnout alarm setting
(8 digits BCD)
+13 to 14
Position-proportional dead band
(8 digits BCD)
+15 to 16
Switching output hysteresis
(8 digits BCD)
+17 to 18
ON/OFF count alarm setting
(8 digits BCD)
+19 to 20
ON/OFF control hysteresis
(8 digits BCD)
+21 to 22
Manual reset (8 digits BCD)
+23 to 24
SP setting lower limit
(8 digits BCD)
+25 to 26
SP setting upper limit
(8 digits BCD)
+27 to 28
SP rise rate limit (8 digits BCD)
+29 to 30
SP fall rate limit (8 digits BCD)
+31 to 32
MV rate-of-change limit (8 digits BCD)
+33 to 34
Secondary loop fixed SP
(8 digits BCD)
+35 to 36
Secondary loop P (8 digits BCD)
+37 to 38
Secondary loop I (8 digits BCD)
+39 to 40
Secondary loop D (8 digits BCD)
+41 to 42
Secondary loop manual reset
(8 digits BCD)
Appendix H
Data
002B (0043 decimal)
00000000 to 09999000
F indicates a negative number.