Omron CS1W-SCU21 Operation Manual page 368

Hide thumbs Also See for CS1W-SCU21:
Table of Contents

Advertisement

ES100# Digital Controller Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Cancel A.T. (Sequence No. 276 (Hex 0114))
Cancels A.T.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Number of units (4 digits Hex)
+2
1st unit
Unit No. (2 digits BCD)
+3
1st unit
PID set No. (4 digits BCD)
+4
2nd unit
Unit No. (2 digits BCD)
+64
32nd unit
Unit No. (2 digits BCD)
+65
32nd unit
(max.)
PID set No. (4 digits BCD)
Number of send data words
+0
Number of units
+1
+2
(Undefined)
+3
(Undefined)
~
+33
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Number of units (4 digits Hex)
+2
1st unit
Unit No. (2 digits BCD)
+3
2nd unit
Unit No. (2 digits BCD)
+33
32nd unit
(max.)
Unit No. (2 digits BCD)
Number of units × 2 + 2
0001 to 0020 (1 to 32 decimal)
00 to 31
0000 to 0008
00 to 31
00 to 31
0000 to 0008
Unit No.
1st unit
Unit No.
2nd unit
~
Unit No.
32nd unit (max.)
Number of units + 2
0001 to 0020 (1 to 32 decimal)
00 to 31
00 to 31
00 to 31
Appendix H
Data
Data
349

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-scu41

Table of Contents