Omron CS1W-SCU21 Operation Manual page 273

Hide thumbs Also See for CS1W-SCU21:
Table of Contents

Advertisement

E5#K Digital Controller Write Protocol
Run/Stop (Sequence No. 072 (Hex 0048))
Switches the mode to Run or Stop according to the command code. This sequence can be executed for multi-
ple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Remote/Local (Sequence No. 073 (Hex 0049))
Switches to remote operation or local operation according to the command mode. This sequence can be exe-
cuted for multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
254
+0
Number of send data words
+1
Number of units
+2
(Undefined)
+3
Command code
+4
(Undefined)
+5
Command code
~
+16
(Undefined)
+17
Command code
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Number of units (4 digits Hex)
+2
1st unit
Unit No. (2 digits BCD)
+3
1st unit
Command code (4 digits BCD)
+17
8th unit
(max.)
Command code (4 digits BCD)
+0
Number of send data words
+1
Number of units
(Undefined)
+2
+3
Command code
+4
(Undefined)
Command code
+5
~
+16
(Undefined)
+17
Command code
Unit No.
1st unit
Unit No.
2nd unit
~
Unit No.
8th unit (max.)
Unit No.
1st unit
Unit No.
2nd unit
~
Unit No.
8th unit (max.)
Appendix D
Data
Number of units × 2 + 2
0001 to 0008
00 to 31
0000:
Run
0001:
Stop
0000:
Run
0001:
Stop

Hide quick links: