Omron CS1W-SCU21 Operation Manual page 318

Hide thumbs Also See for CS1W-SCU21:
Table of Contents

Advertisement

E5#J Temperature Controller Protocol
The E5#J Temperature Controller Protocol performs various settings and controls in remote mode for the Tem-
perature Controller connected to the Serial Communications Unit/Board via RS-232C or RS-422A/485 cable.
Note Negative values cannot be written. All values must be set as unsigned BCD.
Structure of the Protocol
The following table shows the structure of the E5#J Temperature Controller Protocol.
Sequence
Communications
No.
sequence name
200 (00C8)
Select remote mode
201 (00C9)
Select local mode
202 (00CA)
Select backup mode
203 (00CB)
Select RAM write mode Switches from set point write mode to RAM
204 (00CC)
Save set point
205 (00CD)
Write parameters 1
206 (00CE)
Write parameters 2
207 (00CF)
Write input shift value
208 (00D0)
Read parameters 1
209 (00D1)
Read parameters 2
210 (00D2)
Read input shift value
211 (00D3)
Read output value
212 (00D4)
Read process value
213 (00D5)
Read set point limit
214 (00D6)
Read heater current
215 (00D7)
Read initial status
216 (00D8)
General-purpose write
217 (00D9)
General-purpose read
Note 1. The hexadecimal equivalents of sequences numbers are given in parentheses.
2. Ladder Interface Settings
YES: User settings are required for the 3rd or 4th operands of PMCR.
NO:
Send word allocation:
Receive word allocation:Set the constant 0000 for the 4th operand (D).
Appendix G
Function
Switches the Controller to remote mode.
Switches the Controller to local mode.
Switches from set point write mode to backup
mode.
write mode.
Saves the set point.
Writes the set point, alarm value 1, alarm
value 2, and heater burnout alarm value.
Writes the proportional band, integral time,
and derivative time.
Writes the input shift value.
Reads the set point, alarm value 1, alarm
value 2, and heater burnout alarm value.
Reads the proportional band, integral time,
and derivative time.
Reads the input shift value and writes it in
IOM.
Reads the output value and stores it in IOM.
Reads the process value and stores it in
IOM.
Reads the set point limits and stores them in
IOM.
Reads the heater current and stores it in
IOM.
Reads the initial status and stores it in IOM.
Writes the specified parameter by setting a
header code.
Reads the specified parameter by setting a
header code.
Set the constant 0000 for the 3rd operand (S).
Ladder interface
Send word
Receive word
allocation
allocation
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
299