Omron CS1W-SCU21 Operation Manual page 282

Hide thumbs Also See for CS1W-SCU21:
Table of Contents

Advertisement

E5ZE Temperature Controller Read Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
Read Output Values (Sequence No. 102 (Hex 0066))
Reads the output values of the control outputs and stores the results in the specified words.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
+0
Number of receive data words
+1
Process value (rightmost 4 digits)
+2
Process value (leftmost 1 digit)
Process value (rightmost 4 digits)
+3
+4
Process value (leftmost 1 digit)
~
+15
Process value (rightmost 4 digits)
+16
Process value (leftmost 1 digit)
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1
Channel 0
Process value (rightmost 4 digits)
(4 digits BCD)
+2
Channel 0
Process value (leftmost 1 digit)
(1 digit BCD)
+15
Channel 7
Process value (rightmost 4 digits)
(4 digits BCD)
+16
Channel 7
Process value (leftmost 1 digit)
(1 digit BCD)
+0
Number of send data words
+1
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
Number of receive data words
+0
+1
Output value
+2
Cooling output value
+3
Output value
+4
Cooling output value
~
+15
Output value
+16
Cooling output value
~
0011 (0017 decimal)
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
F indicates a negative value.
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
F indicates a negative value.
Unit No.
0002 (fixed)
00 to 0F
Channel 0
Channel 1
~
Channel 7
Appendix E
Channel 0
Channel 1
Channel 7
Data
Data
263