Omron CS1W-SCU21 Operation Manual page 307

Hide thumbs Also See for CS1W-SCU21:
Table of Contents

Advertisement

E5ZE Temperature Controller Write Protocol
Cancel Autotuning (Sequence No. 160 (Hex 00A0))
Cancels Autotuning (AT) for all channels.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Setting Unit (Sequence No. 161 (Hex 00A1))
Writes the setting unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Input Shift Value (Sequence No. 162 (Hex 00A2))
Writes the input shift values.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
288
+0
Number of send data words
(Undefined)
+1
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
Number of send data words
+0
+1
(Undefined)
+2
Write code
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
+2
Write code (4 digits BCD)
+0
Number of send data words
+1
(Undefined)
+2
Input shift value
+3
Input shift value
+4
Input shift value
+5
Input shift value
+6
Input shift value
+7
Input shift value
+8
Input shift value
Input shift value
+9
Unit No.
0002 (fixed)
00 to 0F
Unit No.
0003 (fixed)
00 to 0F
0000: unit of 1
0001: unit of 0.1
Unit No.
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Appendix F
Data
Data

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-scu41

Table of Contents