Omron CS1W-SCU21 Operation Manual page 302

Hide thumbs Also See for CS1W-SCU21:
Table of Contents

Advertisement

E5ZE Temperature Controller Write Protocol
Write Control Period (Sequence No. 153 (Hex 0099))
Writes the control periods and cooling control periods.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
+0
Number of send data words
+1
(Undefined)
+2
Control period
+3
Cooling control period
+4
Control period
+5
Cooling control period
~
Control period
+16
Cooling control period
+17
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
+2
Channel 0
Control period (4 digits BCD)
+3
Channel 0
Cooling control period
(4 digits BCD)
+4
Channel 1
Control period (4 digits BCD)
+5
Channel 1
Cooling control period
(4 digits BCD)
+16
Channel 7
Control period (4 digits BCD)
+17
Channel 7
Cooling control period
(4 digits BCD)
Unit No.
Channel 0
Channel 1
~
Channel 7
0012 (0018 decimal) (fixed)
00 to 0F
0001 to 0099
0001 to 0099
0001 to 0099
0001 to 0099
0001 to 0099
0001 to 0099
Appendix F
Data
283

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-scu41

Table of Contents