Omron CS1W-SCU21 Operation Manual page 379

Hide thumbs Also See for CS1W-SCU21:
Table of Contents

Advertisement

K3T# Intelligent Signal Processor Protocol
Reset (by Unit Number) (Sequence No. 300 (Hex 012C))
This sequence performs the same processing as when an input is received on the reset terminal.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Reset Control (Continuous Units)
(Sequence No. 301 (Hex 012D))
This sequence performs reset control for continuous units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
360
Number of send data words
+0
+1
Number of units
+2
(Undefined)
Relevant unit No.
~
+33
(Undefined)
Relevant unit No.
Offset
Contents (data format)
+0
Number of send data words
(4 digits BCD)
+1
Number of units
(4 digits Hex)
+2
Relevant unit No.
(2 digits BCD)
+33
Relevant unit No.
(2 digits BCD)
+0
Number of send data words
+1
Number of units
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Number of units
(4 digits Hex)
~
0003 to 0022 (3 to 34 decimal)
0001 to 0020 (1 to 32 decimal)
00 to 99
00 to 99
0002
0001 to 0020 (1 to 32 decimal)
Appendix I
Data
Data

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-scu41

Table of Contents