Omron CS1W-SCU21 Operation Manual page 268

Hide thumbs Also See for CS1W-SCU21:
Table of Contents

Advertisement

E5#K Digital Controller Write Protocol
Write Level 1 Parameters 1 (Sequence No. 066 (Hex 0042))
Writes parameters in level 1 (alarm value 1, alarm value 2, alarm value 3, proportional band, integral time, and
derivative time) to multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
+0
Number of send data words
+1
Number of units
+2
(Undefined)
+3
Alarm value 1
+4
Alarm value 2
+5
Alarm value 3
+6
Proportional band
+7
Integral time
+8
Derivative time
~
+51
(Undefined)
+52
Alarm value 1
+53
Alarm value 2
+54
Alarm value 3
+55
Proportional band
Integral time
+56
Derivative time
+57
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Number of units (4 digits Hex)
+2
1st unit
Unit No. (2 digits BCD)
+3
1st unit
Alarm value 1 (4 digits BCD)
+4
1st unit
Alarm value 2 (4 digits BCD)
+5
1st unit
Alarm value 3 (4 digits BCD)
+6
1st unit
Proportional band (4 digits BCD)
+7
1st unit
Integral time (4 digits BCD)
+8
1st unit
Derivative time (4 digits BCD)
+57
8th unit
(max.)
Derivative time (4 digits BCD)
Unit No.
1st unit
~
Unit No.
8th unit (max.)
Number of units × 7 + 2
0001 to 0008
00 to 31
A999 to 9999
F indicates a negative value and A indicates
–1.
A999 to 9999
F indicates a negative value and A indicates
–1.
A999 to 9999
F indicates a negative value and A indicates
–1.
0001 to 9999
0000 to 3999
0000 to 3999
0000 to 3999
Appendix D
Data
249

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1w-scu41

Table of Contents