Omron CS1W-SCU21 Operation Manual page 389

Hide thumbs Also See for CS1W-SCU21:
Table of Contents

Advertisement

K3T# Intelligent Signal Processor Protocol
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
370
+0
Number of send data words
+1
Number of units
(Undefined)
+2
Relevant unit No.
Operand
+3
~
+64
(Undefined)
Relevant unit No.
Operand
+65
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Number of units (4 digits Hex)
+2
Relevant unit No. (2 digits BCD)
+3
Operand (ASCII 2 characters)
+65
Operand (ASCII 2 characters)
+0
Number of receive data words
Peak/bottom data
+1
(Undefined)
+2
(Undefined)
+3
~
+94
Peak/bottom data
+95
(Undefined)
(Undefined)
+96
Offset
Contents (data format)
+0
Number of receive data
words (4 digits Hex)
+1 to +2 Peak/bottom data
(5 digits BCD)
+3
Status
(2 digits Hex)
~
0004 to 0042 (4 to 66 decimal)
0001 to 0020 (1 to 32 decimal)
00 to 99
5048 ("PH")
4248 ("BH")
Same as above
Peak/bottom data
Status
~
Peak/bottom data
Status
0004 to 0061 (4 to 97 decimal)
00000 to 99999
Negative sign: F (most significant digit)
Example 12345
+1
2345
+2
0001
d0 bit:
If overflow:1
d1 bit:
If underflow:1
d2 bit:
Not used
d3 bit:
During forced zero operation:1
(K3TH,K3TR: 0)
d4 bit:
Not used
d5 bit:
During hold input:1
d6 bit:
Bank input 1:1
(K3TH, K3TX: 0)
d7 bit:
Bank input 2:1
(K3TH, K3TX: 0)
Appendix I
Data
Data
Example –1234
+1
1234
+2
F000
Others: 0
Others: 0
Others: 0
Others: 0
Others: 0
Others: 0