E5#K Digital Controller Write Protocol
Write Level 2 Parameters 2 (Sequence No. 069 (Hex 0045))
Writes parameters in level 2 (input digital filter, alarm 1 hysteresis, alarm 2 hysteresis, alarm 3 hysteresis, input
shift upper limit, and input shift lower limit) to multiple units.
Send Data Word Allocation (3rd Operand of PMCR(260))
+0
First word of
send data
+1
+2
+3
+4
+5
+6
+7
+8
+51
+52
+53
+54
+55
+56
+57
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
252
Number of send data words
Number of units
(Undefined)
Input digital filter
alarm 1 hysteresis
alarm 2 hysteresis
alarm 3 hysteresis
Input shift upper limit
Input shift lower limit
~
(Undefined)
Input digital filter
alarm 1 hysteresis
alarm 2 hysteresis
alarm 3 hysteresis
Input shift upper limit
Input shift lower limit
Offset
+0
Number of send data words
(4 digits Hex)
+1
Number of units (4 digits BCD)
+2
1st unit
Unit No. (2 digits BCD)
+3
1st unit
Input digital filter (4 digits BCD)
+4
1st unit
Alarm 1 hysteresis
(4 digits BCD)
+5
1st unit
Alarm 2 hysteresis
(4 digits BCD)
+6
1st unit
Alarm 3 hysteresis
(4 digits BCD)
+7
1st unit
Input shift upper limit (4 digits BCD)
+8
1st unit
Input shift lower limit (4 digits BCD)
+57
8th unit
(max.)
Input shift lower limit (4 digits BCD)
Unit No.
1st unit
~
Unit No.
8th unit (max.)
Contents (data format)
Appendix D
Data
Number of units × 7 + 2
0001 to 0008
00 to 31
0000 to 9999
0001 to 9999
0001 to 9999
0001 to 0099
000 to 9999
000 to 9999
000 to 9999