E5ZE Temperature Controller Write Protocol
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Start Control (Sequence No. 174 (Hex 00AE))
Starts temperature control for all channels in the specified Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Stop Operation or Control (Sequence No. 175 (Hex 00AF))
Stops temperature control or manual operation for all channels of the specified Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of send
data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Start Manual Operation (Sequence No. 176 (Hex 00B0))
Starts manual operation based on the output values that were set for all channels of the specified Unit.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
+0
Number of send data words
+1
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
Number of send data words
+0
(Undefined)
+1
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
Number of send data words
+0
(Undefined)
+1
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
Unit No.
0002 (fixed)
00 to 0F
Unit No.
0002 (fixed)
00 to 0F
Unit No.
0002 (fixed)
00 to 0F