Omron CS1W-SCU21 Operation Manual page 313

Hide thumbs Also See for CS1W-SCU21:
Table of Contents

Advertisement

E5ZE Temperature Controller Write Protocol
Write HB and HS Alarm Valid Channels (Sequence No. 170 (Hex
00AA))
Writes the valid or invalid channels of HB alarm and HS alarm.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
None.
Write Heater Burnout and SSR Failure Detection Current
(Sequence No. 171 (Hex 00AB))
Writes the currents for detecting heater burnouts and SSR failures.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
294
+0
Number of send data words
+1
(Undefined)
+2
(Undefined)
Write code
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Unit No. (2 digits Hex)
+2
Write code (2 digits Hex)
+0
Number of send data words
+1
(Undefined)
+2
Heater burnout detection current
+3
SSR failure detection current
+4
Heater burnout detection current
+5
SSR failure detection current
~
+16
Heater burnout detection current
+17
SSR failure detection current
Unit No.
0003 (fixed)
00 to 0F
00 to FF
Unit No.
Channel 0
Channel 1
~
Channel 7