ES100# Digital Controller Protocol
Read Heater Burnout Data (Sequence No. 253 (Hex 00FD))
Reads the heater burnout alarm in the variable area.
Send Data Word Allocation (3rd Operand of PMCR(260))
First word of
send data
Receive Data Word Allocation (4th Operand of PMCR(260))
Receive data
storage words
322
Offset
Contents (data format)
+128
16th unit
(max.)
Error group 14 data (2 digits Hex)
Error group 15 data (2 digits Hex)
+0
Number of send data words
+1
Number of units
+2
(Undefined)
+3
(Undefined)
~
+33
(Undefined)
Offset
Contents (data format)
+0
Number of send data words
(4 digits Hex)
+1
Number of units (4 digits Hex)
+2
1st unit
Unit No. (2 digits BCD)
+3
2nd unit
Unit No. (2 digits BCD)
+33
32nd unit
(max.)
Unit No. (2 digits BCD)
+0
Number of receive data words
+1
(Undefined)
+2
(Undefined)
+3
(Undefined)
(Undefined)
+4
~
(Undefined)
+32
Offset
Contents (data format)
+0
Number of receive data words
(4 digits Hex)
+1
1st unit
Heater burnout alarm (2 digits Hex)
+2
2nd unit
Heater burnout alarm (2 digits Hex)
+3
3rd unit
Heater burnout alarm (2 digits Hex)
+4
4th unit
Heater burnout alarm (2 digits Hex)
+32
32nd unit
(max.)
Heater burnout alarm (2 digits Hex)
00 to FF
00 to FF
Unit No.
1st unit
Unit No.
2nd unit
~
Unit No.
32nd unit (max.)
Number of units + 2
0001 to 0020 (1 to 32 decimal)
00 to 31
00 to 31
00 to 31
Heater burnout alarm
Heater burnout alarm
Heater burnout alarm
Heater burnout alarm
Heater burnout alarm
Number of units +1
00 to FF
00 to FF
00 to FF
00 to FF
00 to FF
Appendix H
Data
Data
1st unit
2nd unit
3rd unit
4th unit
~
32nd unit (max.)
Data