Terminal Descriptions

Note:
Note:
ST — The default setting for this terminal is the Standby mode controller. As the default setting, this
terminal must be activated for normal system operation. The ST terminal is activated by connecting CC
to this terminal (Sink mode). When deactivated, OFF is flashed on the LED screen and the Not-Ready-
to-Run icon is displayed on the LCD screen as shown in
be programmed to any of the functions listed in
RES — The default setting for this terminal is Reset. The RES terminal is activated by connecting CC
to this terminal (Sink mode). A momentary connection to CC resets the ASD and any fault indications
from the display. Reset is effective when faulted only. This input terminal may be programmed to any
of the functions listed in
F — The default setting for this terminal is the Forward run command. The F terminal is activated by
connecting CC to this terminal (Sink mode). This input terminal may be programmed to any of the
functions listed in
R — The default setting for this terminal is the Reverse run command. The R terminal is activated by
connecting CC to this terminal (Sink mode). This input terminal may be programmed to any of the
functions listed in
S1 — The default setting for this terminal is the Preset Speed 1 (see
terminal is activated by connecting CC to this terminal (Sink mode). This input terminal may be
programmed to any of the functions listed in
S2 — The default setting for this terminal is the Preset Speed 2 (see
terminal is activated by connecting CC to this terminal (Sink mode). This input terminal may be
programmed to any of the functions listed in
S3 — The default setting for this terminal is the Preset Speed 3 (see
terminal is activated by connecting CC to this terminal (Sink mode). This input terminal may be
programmed to any of the functions listed in
S4 — The default setting for this terminal is the Preset Speed 4 (see
terminal is activated by connecting CC to this terminal (Sink mode). This input terminal may be
programmed to any of the functions listed in
RR — The default function assigned to this terminal is Frequency Mode 1. The RR terminal accepts a
0 – 10 VDC input signal that is used to control the function assigned to this terminal. This input terminal
may be programmed to control the speed or torque of the motor via an amplitude setting or regulate by
setting a limit. The gain and bias of this terminal may be adjusted for application-specific suitability
(see
F210
RX — The default function assigned to this terminal is Torque Command. The RX terminal accepts a
±10 VDC input signal that is used to control the function assigned to this terminal. This input terminal
may be programmed to raise or lower the speed or torque of the motor via an amplitude setting or this
terminal may be used to regulate the speed or torque of a motor by setting a limit. The gain and bias of
this terminal may be adjusted for application-specific suitability (see
22
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
The programmable terminal assignments may be accessed and changed from the
default settings as mapped on
Direct Access  Applicable Parameter Number. See the section titled
Mode Menu Navigation on pg. 46
numbers. For further information on terminal assignments and default setting
changes, see the sections titled
pg.
74.
See the section titled
Cable/Terminal/Torque Specifications on pg. 264
conductor and terminal electrical specifications.
Table 5 on pg. 234
Table 5 on pg. 234
Table 5 on pg. 234
– F215). See
pg. 26
for an electrical depiction of the RR terminal.
or via the Direct Access method: Program 
pg. 46
for the applicable Direct Access parameter
Terminal on pg. 47
and
Default Setting Changes on
Figure 22 on pg.
Table 5 on pg. 234
(see F114).
(see F111).
(see F112).
Table 5 on pg. 234
(see F115).
Table 5 on pg. 234
(see F116).
Table 5 on pg. 234
(see F117).
Table 5 on pg. 234
(see F118).
H9 ASD Installation and Operation Manual
Program
for the ASD
32. This input terminal may
(see F113).
Preset Speed 1 on pg.
83). The S1
Preset Speed 2 on pg.
83). The S2
Preset Speed 3 on pg.
84). The S3
Preset Speed 4 on pg.
84). The S4
F216
– F221).