FA33 — Torque Reference from Internal Option PCB
Torque reference is stored as a Hex value in increments of 0.01%/unit.
For example, when torque reference is set up to 50%, it is converted as follows:
50 (%)/0.01 (%/unit) = 5000 (units) = 0x1388 (Hex).
FA50 — Terminal Output Data from Communicatioin
Bit 0 – 6 of terminal output data (FA50) from communication, setting data (0 or 1) can be output to the
output terminal.
Select the functional number 92 – 105 as the selection (F130 – F138, F168, F169) of the output terminal
function before using it.
Bit
0
Communication Data 1 (Output TB Select No.: 92, 93)
1
Communication Data 2 (Output TB Select No.: 94, 95)
2
Communication Data 3 (Output TB Select No.: 96, 97)
3
Communication Data 4 (Output TB Select No.: 98, 99)
4
Communication Data 5 (Output TB Select No.: 100, 101)
5
Communication Data 6 (Output TB Select No.: 102, 103)
6
Communication Data 7 (Output TB Select No.: 104, 105)
7 – 15
FA51 — Analog Output (FM) Data from Communicaiton
The data set as the parameter FA51 can output to FM terminal.
The data adjustment range is 0 – 2047 (resolution: 11 bits).
Select 31 (analog output for communication) as FM terminal meter selection parameter before using it.
Refer to the Meter Setting and Adjustment section of the ASD instruction manual for details.
FA52 — Analog Output (AM) Data from Communication
The data set as the parameter FA52 can output to AM terminal.
The data adjustment range is 0 – 2047 (resolution: 11 bits).
Select 31 (analog output for communication) as AM terminal meter selection parameter before using it.
Refer to the Meter Setting and Adjustment section of the ASD instruction manual for details.
FD00 — Output Frequency (real time)
The current output frequency is read to a resolution of 0.01 Hz per Hex unit.
For example, when the output frequency is 80 Hz, 0x1F40 (Hex) is read.
Since the minimum resolution is 0.01 Hz per unit, 0x1F40 (Hex) = 8000 * 0.01 = 80 Hz.
The following parameters are calculated in a similar fashion.
FD22 — Feedback value of PID (real time). Minimum Unit: 0.01 Hz.
FD16 — PG feedback or Estimated speed (real time). Minimum Unit: 0.01 Hz.
FD29 — Input power (real time). Minimum Unit: 0.01 kW.
FD30 — Output power (real time). Minimum Unit: 0.01 kW.
32
Output TB function name
-
0
Off
-
DeviceNet Module Installation and Operation Manual
1
On
-