F100

Low-Speed Signal Output Frequency

Program Terminal Reach Settings
The Low-Speed Signal Output Frequency parameter sets a frequency
threshold that activates the assigned output terminal for the duration that the
ASD output is equal to or above this setting (see
available output assignments).
each

Speed Reach Frequency

requency
Program Terminal Reach Settings
The Speed Reach Frequency sets a frequency threshold that, when reached or
is within the bandwidth specified by parameter F102, activates the assigned
output terminal for the duration that the ASD output is within the bandwidth
specified (see

Speed Reach Detection Band

Program Terminal  Reach Settings
This parameter sets the bandwidth of the Speed Reach Frequency (F101)
setting.

Forward/Reverse Run Priority Selection

Program Terminal Input Special Functions
The Forward/Reverse Priority Selection determines the operation of the ASD
if the F and R control terminals are activated simultaneously.
Settings:
0 — Reverse
1 — Suspend
The waveforms shown depict the motor response for all combinations of the F
and R terminal settings if the Reverse option is chosen.
The Suspend setting will decelerate the motor to a stop regardless of the
rotation direction when both the F and R control terminals are activated.
86
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Table 8 on pg. 239
for the available output assignments).
Table 8 on pg. 239
for the
Direct Access Number — F100
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F101
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F102
Parameter Type — Numerical
Factory Default — 2.50
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F105
Parameter Type — Selection List
Factory Default — Suspend
Changeable During Run — No
Simultaneous F and R activation.
H9 ASD Installation and Operation Manual
F105