F377

PG Disconnection Detection

Program Feedback PG Settings
This parameter Enables/Disables the system's monitoring of the PG connection
status when using encoders with line driver outputs.
Note:
The PG Vector Feedback Board option is required to use this
feature.
Settings:
0 — Disabled
1 — Enabled with Filter
3 — Enabled (Detect momentary power fail)

Simple Positioning Completion Range

Program Feedback PG Settings
While operating in the Positioning Control mode, this parameter sets the range
of accuracy for a Stop command initiated via the terminal board.
If the setting is too low the stop may be too abrupt.

Autotuning 1

Program Motor Vector Motor Model
This parameter sets the Autotune command status.
Selecting Reset Motor Defaults for this parameter sets parameters F410, F411,
F412, and
F413
to the factory default settings.
If selecting Autotune on Run Command, Autotune Initiated by Input
Terminal, or Autotune of Detail Parameters for this parameter set the Base
Frequency, Base Frequency Voltage, and the Motor Rated Revolutions to
the nameplated values of the motor to achieve the best possible Autotune
precision.
Settings:
0 — Autotune Disabled
1 — Reset Motor Defaults
2 — Enable Autotune on Run Command
3 — Autotuning by Input Terminal Signal (see
4 — Motor Constant Auto Calculation

Slip Frequency Gain

Program Motor  Vector Motor Model
This parameter provides a degree of slip compensation for a given load. A
higher setting here decreases the slip allowed for a given load/ASD output ratio.
H9 ASD Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Table 5 on pg.
234)
Direct Access Number — F377
Parameter Type — Selection List
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Direct Access Number — F381
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 1
Maximum — 4000
Direct Access Number — F400
Parameter Type — Selection List
Factory Default — Autotune Disabled
Changeable During Run — No
Direct Access Number — F401
Parameter Type — Numerical
Factory Default — 70
Changeable During Run — Yes
Minimum — 0
Maximum — 150
Units — %
F401
151