My Function Percent Data - Toshiba H9 ASD Installation And Operation Manual

Adjustable low voltage heavy duty industrial speed drive
Hide thumbs Also See for H9 ASD:
Table of Contents

Advertisement

F916
Input Function Target 3
Program My Function My Function Unit 3
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Input Function Target 3
terminal.
This setting assigns the function of the programmable Input Function Target 3
terminal to any one of the user-selectable functions listed in
Table 8 on pg.
239, or
See
F977
for more information on this parameter.
Output Function Assigned
Program My Function My Function Unit 3
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the Output Function Assigned terminal.
This setting assigns the function of the programmable Output Function
Assigned data location to one of the functions listed in the Input Setting field
of
Table 8 on pg.
239.
Settings:
0 – 3099
See the My Function Instruction Manual (P/N E6581335) and
information on this parameter.

My Function Percent Data 1

Program My Function My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the My Function Percent Data 1.
The analog signal is selected using the Input Setting number from
pg.
239.
Once the assigned output value reaches the threshold setting of this parameter
the output value is transferred to My Function Out 1.
See the My Function Instruction Manual (P/N E6581335) and
information on this parameter.
My Function Percent Data 2
Program My Function My Function Data
This parameter is used to set the trigger threshold level of the analog signal of
the My Function Percent Data 2.
The analog signal is selected using the Input Setting number from
pg.
239.
H9 ASD Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Table 10 on pg.
241.
Direct Access Number — F916
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
Table 7 on pg.
238,
Direct Access Number — F917
Parameter Type — Selection List
Factory Default — 0 (Disabled)
Changeable During Run — Yes
F977
for more
Direct Access Number — F918
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Table 8 on
Maximum — 200.00
Units — %
F977
for more
Direct Access Number — F919
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Table 8 on
Maximum — 200.00
Units — %
F919
217

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

P9 asd

Table of Contents