F342

Torque Bias Input Selection

Program Torque Torque Control
Once enabled at parameter F341, this parameter sets the source of the input
signal that will set the torque level used to provide the Braking Mode
Selection function of parameter F341.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — EOI (Keypad)
5 — RS485 2-Wire
6 — RS485 4-Wire
7 — Communication Option Board
8 — RX2 Option (AI1)
Panel Torque Bias
Program Torque Torque Control
Once enabled at parameter F341, this parameter establishes the torque bias
setting to which the setting of
produce the final torque value used to carry out the Braking Mode Selection
function of parameter F341.
Panel Torque Gain
Program Torque Torque Control
Once enabled at parameter F341, this parameter sets the sensitivity of the
torque control source selected at
function of parameter F341.

Release Time

Program Torque Torque Control
Once enabled at parameter F341, this parameter sets the time that the brake will
hold after the requirements of the Braking Mode Selection function of
parameter
F341
have been met.

Creeping Frequency

Program Torque Torque Control
Once enabled at parameter F341, and while running, upon receiving a Stop
command this parameter sets an output frequency to be provided for the
duration of the time setting of parameter F347.
H9 ASD Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
F342
will either add to or subtract from to
F342
for the Braking Mode Selection
Direct Access Number — F342
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F343
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — -250.00
Maximum — +250.00
Units — %
Direct Access Number — F344
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.00
Units — %
Direct Access Number — F345
Parameter Type — Numerical
Factory Default — 0.05
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Direct Access Number — F346
Parameter Type — Numerical
Factory Default — 3.00
Changeable During Run — Yes
Minimum —
F240
Setting
Maximum — 20.0
Units — Hz
F346
143