Upper-Limit Frequency; Lower-Limit Frequency; Base Frequency 1; V/F Pattern - Toshiba H9 ASD Installation And Operation Manual

Adjustable low voltage heavy duty industrial speed drive
Hide thumbs Also See for H9 ASD:
Table of Contents

Advertisement

F012

Upper-Limit Frequency

Program Fundamental Frequency Settings
This parameter sets the highest frequency that the ASD will accept as a
frequency command or frequency setpoint. The ASD may output frequencies
higher than the Upper-Limit Frequency (but, lower than the Maximum
Frequency) when operating in the PID Control mode, Torque Control mode,
or the Vector Control modes (sensorless or feedback).
Note:
This setting may not be higher than the Maximum Frequency
(F011) setting.

Lower-Limit Frequency

Program Fundamental Frequency Settings
This parameter sets the lowest frequency that the ASD will accept as a
frequency command or frequency setpoint. The ASD will output frequencies
lower than the Lower-Limit Frequency when accelerating to the lower-limit or
decelerating to a stop. Frequencies below the Lower-Limit may also be output
when operating in the PID Control mode, Torque Control mode, or the
Vector Control modes (sensorless or feedback).

Base Frequency 1

Program Fundamental Motor Set 1
The Base Frequency 1 setting is the frequency at which the output voltage of
the ASD reaches its maximum setting. The Base Frequency Voltage 1
parameter is set at F409.
For proper motor operation, the Base Frequency should be set for the
nameplated frequency of the motor.

V/f Pattern

Program Fundamental Frequency Settings
This function establishes the relationship between the output frequency and the
output voltage.
Bolded selections use the motor tuning parameters of the drive to properly
configure the ASD for the motor being used. If Load Reactors or Long Lead
Filters are used, or if the capacity of the ASD is greater than the motor, manual
tuning of the motor parameters may be required for optimum performance.
Settings:
0 — Constant Torque
1 — Voltage Decrease Curve
2 — Automatic Torque Boost
3 — Sensorless Vector Control (Speed)
4 — Sensorless Vector Control (Speed/Torque Switching)
5 — V/f 5-point Curve (Go to
6 — PM Drive (Permanent Magnet)
7 — PG Feedback Vector Control (Speed)
8 — PG Feedback Vector Control (Speed/Torque Switching)
When operating in the Vector Control mode the carrier
Note:
frequency should be set to 2.2 kHz or above
H9 ASD Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
F190
to configure the V/f 5-Point Settings)
.
Direct Access Number — F012
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F013
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper-Limit (F012)
Units — Hz
Direct Access Number — F014
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Upper-Limit (F012)
Units — Hz
Direct Access Number — F015
Parameter Type — Selection List
Factory Default — Constant Torque
Changeable During Run — No
F015
81

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

P9 asd

Table of Contents