F692
MON 2 Output Gradient Characteristic
Program Terminal Analog Output Terminals
This parameter sets the output response polarity of the MON2 output terminal.
The MON2 output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See parameter
F672
for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
MON 2 Bias Adjustment
Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the MON2 terminal.
Set the assigned function of parameter
to a zero output.
See parameter
F674
for more information on this setting.
Parameter Write Lock Out
Program Utilities Prohibition
This parameter Enables/Disables the Run and Stop keys.
Settings:
0 — Enabled
1 — Disabled
Display Units for Voltage and Current
Program Utilities Display Parameters
This parameter sets the unit of measurement for current and voltage values
displayed on the EOI.
Settings:
0 — %
1 — A/V
Display Unit Multiplication Factor
Program Utilities Display Parameters
This parameter provides a multiplier for the displayed speed value shown on the
EOI of the ASD.
This parameter may be used to display the rate that a commodity is being
processed by the driven load in process units (i.e., units/time).
Example: An output frequency of 100 Hz would be displayed as 50 Hz if
using a multiplier of 0.5 for this parameter.
Note:
PID frequency-limiting parameters are not affected by this
setting (i.e., F364, F365, F367, and F368).
196
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
F674
to zero and then set this parameter
Direct Access Number — F692
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
Direct Access Number — F693
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — 100.0
Units — %
Direct Access Number — F700
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
Direct Access Number — F701
Parameter Type — Selection List
Factory Default — %
Changeable During Run — Yes
Direct Access Number — F702
Parameter Type — Numerical
Factory Default — 0.00 (OFF)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.00
H9 ASD Installation and Operation Manual
F702