Input Terminal Priority; 16-Bit Binary/Bcd Input - Toshiba H9 ASD Installation And Operation Manual

Adjustable low voltage heavy duty industrial speed drive
Hide thumbs Also See for H9 ASD:
Table of Contents

Advertisement

F106

Input Terminal Priority

Program Terminal Input Special Functions
This parameter is used to allow the Jog and DC Injection Braking input
signals to control the ASD when received via the Terminal Board even though
the system is in the Local mode.
With this parameter enabled, a Jog command or a DC Injection Braking
command received from the Terminal Board will receive priority over
commands from the EOI.
See
F260
for more information on using the Jog function.
See
F250
F252
for more information on DC Injection Braking.
Settings:
0 — Disabled
1 — Enabled

16-Bit Binary/BCD Input

Program Terminal Input Special Functions
The extended terminal function is used with the Expansion IO Card Option
(P/N ETB004Z).
This parameter defines the format of the binary or BCD data when using the
option card.
Note:
The Expansion IO Card Option 2 option board is required to
use this terminal.
See the Expansion IO Card Option 1 instruction manual (P/N 58685) for
more information on the function of this terminal.
Settings:
0 — None
1 — 12-Bit Binary
2 — 16-Bit Binary
3 — 3-Digit BCD
4 — 4-Digit BCD
5 — Inverted 12-Bit Binary
6 — Inverted 16-Bit Binary
7 — Inverted 3-Digit BCD
8 — Inverted 4-Digit BCD
Selections using 16-bit binary or 4-digit BCD will require the configuration of
terminals S1-S4 on the Terminal Board as binary bits 0 – 3
Frequency Mode 1 (F004) parameter must be set to Binary/BCD.
For proper scaling of the binary or BCD input, parameters
configured.
H9 ASD Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Direct Access Number — F106
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Direct Access Number — F107
Parameter Type — Selection List
Factory Default — None
Changeable During Run — No
(F115 –
F118). The
F228
F231
must be
F107
87

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

P9 asd

Table of Contents