Fm Output Terminal Function; Fm Output Terminal Adjustment - Toshiba H9 ASD Installation And Operation Manual

Adjustable low voltage heavy duty industrial speed drive
Hide thumbs Also See for H9 ASD:
Table of Contents

Advertisement

F005

FM Output Terminal Function

Program Terminal Analog Output Terminals
This parameter is used to set the output function of the FM analog output
terminal. The FM output terminal produces an output current or voltage that is
proportional to the magnitude of the function assigned to this terminal (select
current or voltage at F681). The available assignments for this output terminal
are listed in
Table 6 on pg.
Note: To read voltage at this terminal connect a 100 – 500 resistor from
the FM (+) terminal to the CC (-) terminal. Using a voltmeter read
the voltage across the 100 – 500 resistor.
To read current at this terminal connect a 100 – 500 resistor from
the FM (+) terminal through a series Ammeter to the CC (-) terminal.
The FM analog output has a maximum resolution of 1/1024 and a
maximum load rating of 500 ohms.
FM Terminal Setup Parameters
F005
— Set FM Function
F006
— Calibrate FM Terminal
F681
— Voltage/Current Output Switching Selection
F682
— Output Response Polarity Selection
F683
— Set Zero Level

FM Output Terminal Adjustment

Program Terminal Analog Output Terminals
This parameter is used to calibrate the FM analog output.
To calibrate the FM analog output, connect a meter (current or voltage) as
described at F005.
With the drive running at a known value (e.g., output frequency), adjust this
parameter until the assigned function produces the desired DC level output at
the FM output terminal.
See
F005
for more information on this setting.
78
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
237.
Direct Access Number — F005
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
Direct Access Number — F006
Parameter Type — Numerical
Factory Default — 493
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
H9 ASD Installation and Operation Manual