F003
Command Mode Selection
Program Fundamental Standard Mode Selection
The Command Mode Selection establishes the source of the command input
for the ASD. Command inputs include Run, Stop, Forward, etc. The Override
feature may supersede the Command Mode Selection setting (see
Mode and Frequency Mode Control on pg.
Settings:
0 — Terminal Block
1 — Not Used
2 — EOI (Keypad)
3 — RS485
4 — Communication Option Board
Frequency Mode 1
Program Fundamental Standard Mode Selection
The Frequency Mode 1 setting establishes the source of the frequency-control
input for the ASD. The Frequency Mode 2 setting or the Override feature may
supersede the Frequency Mode 1 setting.
Note:
Only Bolded items from the Settings list below may be placed in
the Override Mode. See the section titled
Frequency Mode Control on pg. 36
Override feature.
Settings:
1 — V/I
2 — RR
3 — RX
5 — EOI (Keypad)
6 — RS485
7 — Communication Option Board
8 — RX2 Option (AI1)
9 — Option V/I
10 — UP/DOWN Frequency
11 — Pulse Input (Option)
12 — Pulse Input (Motor CPU)
13 — Binary/BCD Input (Option)
H9 ASD Installation and Operation Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Command
36).
Command Mode and
for more information on the
Direct Access Number — F003
Parameter Type — Selection List
Factory Default — Terminal Block
Changeable During Run — No
Direct Access Number — F004
Parameter Type — Selection List
Factory Default — RR
Changeable During Run — No
F004