F202

V/I Input Point 1 Frequency

Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the V/I input terminal when
the V/I terminal is used as the control input while operating in the Speed
Control mode.
This parameter sets V/I Input Point 1 Frequency and is the frequency that is
associated with the setting of V/I Input Point 1 Setting when operating in the
Speed Control mode.
See V/I Input Point 1 Setting (F201) for more information on this setting.

V/I Input Point 2 Setting

Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the V/I input terminal when
the V/I terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This parameter sets the V/I input level that is associated with V/I Input Point 2
Frequency when operating in the Speed control mode or is associated with the
V/I Input Point 1 Rate when operating in the Torque Control mode.
This value is entered as 0% to 100% of the V/I input signal range.
See V/I Input Point 1 Setting (F201) for more information on this setting
when used for Speed control.
See V/I Input Point 1 Rate (F203) for more information on this setting when
used for Torque Control.

V/I Input Point 2 Frequency

Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the V/I input terminal when
the V/I terminal is used as the control input while operating in the Speed
Control mode.
This parameter sets V/I Input Point 2 Frequency and is the frequency that is
associated with the setting of V/I Input Point 2 Setting when operating in the
Speed Control mode.
See V/I Input Point 1 Setting (F201) for more information on this setting.
106
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Direct Access Number — F202
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F203
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Direct Access Number — F204
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz