Feedback (Inst) — Provides a status of the Real Time Feedback in Hz.
Feedback (1 Second) — Provides a status of the 1-Second Averaging feedback in Hz.
Torque — Displays the Output Torque as a percentage of the rated capacity of the H9 ASD.
Torque Reference — Displays the Torque Reference as a percentage of the maximum torque
available.
Torque Current — Displays the torque-producing current value.
Excitation Current — Displays the current value required to produce the excitation field.
PID Feedback — Provides a status of the PID Real Time Feedback in Hz.
Input Power — Displays the Input Power in Kilowatts (kW).
Output Power — Displays the Output Power in Kilowatts (kW).
Pattern Group Number — Displays the active Pattern Run Group Number.
Pattern Group Cycle — Displays the cycle number of the active Pattern Run Group.
Pattern Group Preset — Displays the active Preset Speed being run of the active Pattern Run
Group.
Pattern Time — Displays the remaining time for the active Pattern Run Group.
RR — Displays the RR input value as a percentage of the full range of the RR value (potentiometer
input).
V/I — Displays the V/I input setting as a percentage of the full range of the V/I value.
Note:
RX — Displays the RX input setting as a percentage of the full range of the RX value (-10 to
+10 VDC input).
RX2 Option (AI1) — Displays the RX2 input setting as a percentage of the full range of the RX2
value.
Note:
Trip Code — Displays None if there are no errors, or displays one of the associated Fault Codes
listed in
Past Trip 1 — This function records and displays the last trip incurred. Subsequent trips will replace
Past Trip 1. As trip records are replaced they are shifted to the next level of the Past Trip locations
until being deleted (i.e., Past Trip 1 is moved to Past Trip 2 and then to Past Trip 3 until being
shifted out of Past Trip 4). Once shifted out of Past Trip 4 the record is deleted. If no trips have
occurred since the last reset, No Error is displayed for each trip record.
Past Trip 2 — Past trip information or None.
Past Trip 3 — Past trip information or None.
44
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
The isolated V/I input terminal may receive Current or Voltage to control the
output speed or the output torque. The input signal type must be selected at
on the Terminal Board.
The V input setting of
SW301
the I input setting of
SW301
may be used as a frequency or torque command source. See parameter
more information on the setup of this terminal.
The RX2 function is available on the Expansion IO Card Option 1 option board
(P/N ETB003Z) only.
Table 14 on page 248
if there is an active Fault (e.g., E = Emergency Off).
is used for the 0 – 10 VDC analog input signal and
is used for the 0 – 20 mA analog input signal. Either
H9 ASD Installation and Operation Manual
SW301
F201
for